Step 1 · Service and factored loads
- Ps510 kN/m
PDL + PLL = 290 + 220
- Pu700 kN/m ← governs
1.2PDL + 1.6PLL = 1.2(290) + 1.6(220)
- Pu406 kN/m
1.4PDL = 1.4(290)
NSCP 2015 · Section 413
Enter the given loads, dimensions and soil data. The footing size, thickness, bar count, spacing and development lengths are solved step by step.
Therefore, use
PDL + PLL = 290 + 220
1.2PDL + 1.6PLL = 1.2(290) + 1.6(220)
1.4PDL = 1.4(290)
qa − γc·hc − γs(Df − hc) − qs = 193 − 23.5(0) − 15.74(1.2 − 0) − 0
Ps / qe = 510 / 174.112
Pu / B = 700 / 3
φ(1/6)λ√fc'·b·d = qu((B − a)/2 − d) · 0.75(1/6)(1)√20.7(1)(d)(1000) = 233.333(1.35 − d)
d + cc + ½db = 392.744 + 75 + 10
qa − γc·hc − γs(Df − hc) − qs = 193 − 23.5(0.5) − 15.74(1.2 − 0.5) − 0
Ps / qe = 510 / 170.232
Pu / B
one-way shear: φVc = qu(1.35 − d)
hc − cc − ½db = 500 − 75 − 10
∴ Use 3 m wide × 0.5 m thick wall footing
qu·x²/2, x = (B − a)/2 = 1.35 m
(459/1600)β1·fc'·b·d²(1 − 3β1/16), β1 = 0.85
Mu / (φbd²) = 212.625×10⁶ / (0.90 × 1,000 × 415²)
0.85fc'/fy [1 − √(1 − 2Rn/0.85fc')]
1.4 / fy = 1.4 / 415
ρbd = 0.00345(1,000)(415)
1000·Ab / As = 1000(π/4·20²) / 1,429.85
lesser of 3hc = 1,500 mm and 450 mm
s provided ≤ smax
∴ Use 20 mm ∅ main bars spaced 200 mm O.C.
0.002·B·hc = 0.002(3,000)(500)
As / Ab = 3,000 / (π/4·16²)
(B − 2cc − db) / (N − 1)
lesser of 5hc = 2,500 and 450 mm
∴ Use 15 pcs − 16 mm ∅ temperature bars spaced uniformly O.C.
bottom bars, uncoated
lesser of cc + db/2 = 85 and s/2 = 100
85 / 20 = 4.25
(1/1.1)(fy/λ√fc')(ψtψeψs/((cb+Ktr)/db))·db ≥ 300
from critical section to bar end, less cover
0.24fyψr/(λ√fc')·db = 0.24(415)/√20.7 (10)
0.043fyψr·db = 0.043(415)(10)
minimum
hc − cc − bar layers
∴ The height of footing is adequate
greater of 0.071fy·db = 294.65 mm and 300 mm, × 4/3 since fc' < 21 MPa
∴ Use lap splice = 400 mm
Design aid based on NSCP 2015 Vol. 1 (Sections 406, 413, 422, 425). Results should be reviewed and signed by a licensed civil engineer before construction.